TMF Series 3 Phase Input - 1 Phase Output 10 kVA - 20 kVA Online UPS


TMF  Series of three phases in / single phase out with high frequency online double conversion UPS is a stable and reliable UPS system designed according to international power grid environment and network systems requirements. Its excellent quality and perfect usability provide safe network power supply with reliable protection and satisfy the users requirements of protecting overall equipment.


  • DSP Processor Technology
  • High Frequency Double Conversion Technology
  • Wide Input Voltage Range; 110- 300 Vac
  • Input PFC
  • Output Power Factor 0,9
  • Selectable Battery Voltage ; 192 / 240 Vdc.
  • Selectable End of Discharge Battery Voltage (EOD) from Panel
  • 3/1 Phase or 1/1 Phase Operating Options
  • Cold Start
  • Zero Transfer Time
  • Energy Saving with Eco Mode
  • Smart Battery Management
  • Generator Compatible Operation
  • Charges Batteries While UPS OFF
  • Automatic Controlled Fan Speed
  • Standard RS 232 Communication
  • RS 485/SNMP/AS400/USB Com. Ports (Optional)
  • Emergency Power Off (EPO) (Optional)
  • Manual ByPass (Optional)
  • N+1 Parallel Operation (Optional)
  • Adding Extra Batteries for More Backup (Optional)
  • Electromagnetic Compatibility
MODEL TMF-10 TMF-15 TMF-20
POWER  10.000 VA / 9.000 W 15.000 VA / 13.500 W 20.000 VA / 18.000 W
INPUT
Voltage 220/380 Vac 3 Phase Input/1 Phase Output or  1 Phase Input/1 Phase Output
Voltage Tolerance 1 Phase Input; %100 Lineer Load (176-275) ± 5Vac, %50 Lineer Load (120-176) ± 5Vac 
3 Phase Input; %100 Lineer Load (304-476) ± 5Vac, %50 Lineer Load (208-304) ± 5Vac
Frequency  50/60 Hz
Frequency Range 40Hz-70Hz / (45Hz-55Hz 54Hz-66Hz @ Load>60% and 1 Phase Input / 1 Phase Output)
Power Factor 3 Phase Input≥ 0,9 / 1 Phase Input ≥ 0,9
THDi Lineer Load ≤ %2 / Non Lineer Load ≤ %4
OUTPUT
Voltage 220 / 230 / 240 Vac – Adjustable LCD Panel
Voltage Regulation ± %1
Frequency 50 / 60 Hz
Wave Form Pure Sine Wave 
Power Factor 0,9
Crest Factor 3:1
THDv Lineer Load ≤ %1; Non Lineer Load ≤ %5
Transfer Time 0 ms ( Line- Battery )
Overload Capacity 100%-105% Continuous, 1 min @105-125% Load, 30 sec @125-150% Load, 0.5 sec @>150% Load
EFFICIENCY
On-Line Mode ≥ %94
Eco Mode ≥ %98
BATTERY
Battery Voltage 192 Vdc 192 / 216 / 240 Vdc
Battery Quantity 16 16 / 18 / 20 Adjustable via LCD Panel
Battery Charging Current 4 A
Battery Charging Time Varies depending on battery capacity
GENERAL FEATURES
Display LCD
RS 232 Yes
EPO (Emergency Power OFF) Optional
Communication Slot Optional
Monitor Software Winpower
Parallel Working 3 A (Optional)
Frequency Converter Mode Yes (1 Phase Input / 1 Phase Output Operation, 60% Power Reduction)
Maintenance ByPass Optional
ENVIRONMENTAL
Operating Temperature 0 ˚C- 40 ˚C  
Relative Humidity 20%-90% (Non-condensing)
Acoustic Noise 60 dB@1m.
Ingress Protection Level IP 20
Altitude 0-3000m (1% power loss for every 100m)
STANDARDS
Harmonized Standards EN 62040-1, EN 62040-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-3, EN 61000-4-5
PHYSICAL
Dimensions (WxDxH) mm 212 x 500 x 420 248 x 500 x 565 248 x 500 x 616
Weight (kg) 16,9; 20 31; 35