Online UPS
TMF Series 3 Phase Input - 1 Phase Output 10 kVA - 20 kVA Online UPS
TMF Series of three phases in / single phase out with high frequency online double conversion UPS is a stable and reliable UPS system designed according to international power grid environment and network systems requirements. Its excellent quality and perfect usability provide safe network power supply with reliable protection and satisfy the users requirements of protecting overall equipment.
- DSP Processor Technology
- High Frequency Double Conversion Technology
- Wide Input Voltage Range; 110- 300 Vac
- Input PFC
- Output Power Factor 0,9
- Selectable Battery Voltage ; 192 / 240 Vdc.
- Selectable End of Discharge Battery Voltage (EOD) from Panel
- 3/1 Phase or 1/1 Phase Operating Options
- Cold Start
- Zero Transfer Time
- Energy Saving with Eco Mode
- Smart Battery Management
- Generator Compatible Operation
- Charges Batteries While UPS OFF
- Automatic Controlled Fan Speed
- Standard RS 232 Communication
- RS 485/SNMP/AS400/USB Com. Ports (Optional)
- Emergency Power Off (EPO) (Optional)
- Manual ByPass (Optional)
- N+1 Parallel Operation (Optional)
- Adding Extra Batteries for More Backup (Optional)
- Electromagnetic Compatibility
| MODEL | TMF-10 | TMF-15 | TMF-20 | |
| POWER | 10.000 VA / 9.000 W | 15.000 VA / 13.500 W | 20.000 VA / 18.000 W | |
| INPUT | ||||
| Voltage | 220/380 Vac 3 Phase Input/1 Phase Output or 1 Phase Input/1 Phase Output | |||
| Voltage Tolerance | 1 Phase Input; %100 Lineer Load (176-275) ± 5Vac, %50 Lineer Load (120-176) ± 5Vac | |||
| 3 Phase Input; %100 Lineer Load (304-476) ± 5Vac, %50 Lineer Load (208-304) ± 5Vac | ||||
| Frequency | 50/60 Hz | |||
| Frequency Range | 40Hz-70Hz / (45Hz-55Hz 54Hz-66Hz @ Load>60% and 1 Phase Input / 1 Phase Output) | |||
| Power Factor | 3 Phase Input≥ 0,9 / 1 Phase Input ≥ 0,9 | |||
| THDi | Lineer Load ≤ %2 / Non Lineer Load ≤ %4 | |||
| OUTPUT | ||||
| Voltage | 220 / 230 / 240 Vac – Adjustable LCD Panel | |||
| Voltage Regulation | ± %1 | |||
| Frequency | 50 / 60 Hz | |||
| Wave Form | Pure Sine Wave | |||
| Power Factor | 0,9 | |||
| Crest Factor | 3:1 | |||
| THDv | Lineer Load ≤ %1; Non Lineer Load ≤ %5 | |||
| Transfer Time | 0 ms ( Line- Battery ) | |||
| Overload Capacity | 100%-105% Continuous, 1 min @105-125% Load, 30 sec @125-150% Load, 0.5 sec @>150% Load | |||
| EFFICIENCY | ||||
| On-Line Mode | ≥ %94 | |||
| Eco Mode | ≥ %98 | |||
| BATTERY | ||||
| Battery Voltage | 192 Vdc | 192 / 216 / 240 Vdc | ||
| Battery Quantity | 16 | 16 / 18 / 20 Adjustable via LCD Panel | ||
| Battery Charging Current | 4 A | |||
| Battery Charging Time | Varies depending on battery capacity | |||
| GENERAL FEATURES | ||||
| Display | LCD | |||
| RS 232 | Yes | |||
| EPO (Emergency Power OFF) | Optional | |||
| Communication Slot | Optional | |||
| Monitor Software | Winpower | |||
| Parallel Working | 3 A (Optional) | |||
| Frequency Converter Mode | Yes (1 Phase Input / 1 Phase Output Operation, 60% Power Reduction) | |||
| Maintenance ByPass | Optional | |||
| ENVIRONMENTAL | ||||
| Operating Temperature | 0 ˚C- 40 ˚C | |||
| Relative Humidity | 20%-90% (Non-condensing) | |||
| Acoustic Noise | ≤ 60 dB@1m. | |||
| Ingress Protection Level | IP 20 | |||
| Altitude | 0-3000m (1% power loss for every 100m) | |||
| STANDARDS | ||||
| Harmonized Standards | EN 62040-1, EN 62040-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-3, EN 61000-4-5 | |||
| PHYSICAL | ||||
| Dimensions (WxDxH) mm | 212 x 500 x 420 | 248 x 500 x 565 | 248 x 500 x 616 | |
| Weight (kg) | 16,9; 20 | 31; 35 | ||